File #: LN-62    Version: Name:
Type: DRC Submission Status: Regular Agenda Ready
File created: 12/22/2020 In control: Development Review Committee
On agenda: 5/4/2022 Final action:
Title: THE NEW AUTO TOY STORE
Attachments: 1. 1/6/21 DRC Meeting Drawings, 2. 1/6/21 DRC Meeting Documents, 3. DRC Documents_5.4.2022.zip, 4. DRC Drawings_5.4.2022.zip

boardname

Development Review Committee

Meeting Date: May 4, 2022

 

title

THE NEW AUTO TOY STORE

 

projectinfo

Request:                     Major Site Plan

P&Z#                     20-12000049

Owner:                     JMPM Investment Co Ltd

Project Location:                     929, 941 SW 8th St

Folio Number:                     494202030870, 494202030880

Land Use Designation:                     I (Industrial )

Zoning District:                     I-1 (General Industrial)

Commission District:                     5 (Cyndy Floyd)

Agent:                      Paola A. West (954-529-9417)

Project Planner:                     Lauren Gratzer (954-545-7792) /                                  lauren.gratzer@copbfl.com

 

otherinfo

 

 

Summary:                     

The Applicant is requesting MAJOR SITE PLAN approval in order to construct a 6,672 square foot building addition with associated parking and landscape updates. This project previous came in as a Minor Site Plan, however, the scope of work has since increased. This is a resubmittal from the January 6, 2021 DRC meeting.

 

 

 

Staff Conditions:                      

PLANNING

Plan Reviewer: Daniel Keester O’Mills | daniel.keester@copbfl.com

Status: Review Complete Pending Development Order

 

-Land use for this parcel is Industrial, the zoning is I-1 (General Industrial). The site plan design/layout appears to have changed & no longer includes auto sales with outdoor display. The applicant obtained a special exception for that use, as noted in the narrative (P&Z: 20-17000009) from the Zoning Board of Appeals, but it doesn''t seem to be relevant any longer. The proposal was originally limited to site improvements, but the current site plan proposes a new 2 story 6,600 square foot building for vehicle display. This is now a Major Site Plan application, which will require the submittal of a revised fee and new comments from Zoning will be issued based on the revised scope.


-The property is platted (FAIRVIEW AMENDED PLAT; ORB 10 Pg 25). When recorded, the plat did not include any plat notes or restrictions to the development of the property.


-The city has sufficient capacity to accommodate the proposal.


-The property is accessed from SW 8th Street. SW 8th Street is within a non-residential zoning district, not specifically listed in the Trafficways Plan or Code of Ordinances (100.01 Minimum right-of-way). The 60 feet provided on SW 8th Street is sufficient.


-The property does not abut any right-of-way identified on the Broward County Trafficways Plan.

 

 

ENGINEERING DEPARTMENT

Plan Reviewer: David McGirr | david.mcgirr@copbfl.com

Status: Review Complete Resubmittal Required

 

The following comments must be addressed prior to the submission of these plans to the Building Division for formal plan review and permitting:

1. Place note on landscape plans as per City Ordinance(s) §50.02(A) (4) and §100.35(E), that landscaping materials other than sod are not allowed within (5'') five feet of any portion of City owned utilities within the public street right-of-way including meters, hydrants, service lines etc. Also, please note that no trees, shrubbery or obstruction shall be placed within a 3’ radius of a City-owned sewer lateral cleanout or water &/or reuse meter. Show the location of all existing City owned and maintained potable water mains and services, sanitary sewer mains or laterals and storm drainage lines on the proposed landscape plans. Contact the Engineering Div. for Utility information. Engineering Standard street tree detail 316-1

2. The proposed paving, grading and drainage plans must be approved by the Broward County EPD Surface Water Management Division.

3. Conceptual civil plan design lacked detail and specifics. Nor did the design properly delineate the adjacent City mains, sizes or connection size and characteristics. How are the new buildings being supplied with water and sewer?

4. At time of permitting submit an Engineering permit application for the proposed onsite and offsite paving.
5. At time of permitting submit a copy of a signed agreed upon contract or a schedule of values for the proposed onsite and offsite paving. Please include sub-base, limerock, prime and asphalt or concrete. Per page two of the Engineering Application: In order to determine permit fees, please provide an executed contract between the registered property owner and the contractor performing the proposed work.

**** Please note - additional review comments may be issued by the City Engineering Division throughout the remainder of the permitting process while the civil engineering plans are being finalized for this project. ****

 

 

FIRE DEPARTMENT

Plan Reviewer: Jim Galloway | jim.galloway@copbfl.com

Status: Review Complete Resubmittal Required

 

1 - what is the total square footage of the building? provide greater detail of buildings fire separation. include existing or proposed fire protection and life safety systems.
3 - depending on occupancy classification and sqft footage this building may require fire sprinklers as per Florida Fire Prevention Code 7th Edition NFPA 101.
3 - Provide site plan with civils showing location of existing and proposed fire hydrants.

 

 

BUILDING DIVISION

Todd Stricker | todd.stricker@copbfl.com

Status: Review Complete Pending Development Order

 

Advisory Comments
A preliminary examination of the documents has been performed; additional comments may apply when completed plans and/or specifications have been submitted for permitting to the building department.
Buildings shall comply with all local, state and federal codes in effect at time of application, including FEMA Floodplain, NPDES and HVHZ regulations.

FBC_BCA 105.2.3 Public service agencies/other approvals. The building official shall require that the laws, rules and regulations of any other regulatory AHJ, and where such laws, rules and regulations are applicable and are known to the building official, shall be satisfied before a permit shall be issued. The building official shall require such evidence, as in his or her opinion is reasonable, to show such other approvals.

City Ordinance 53.16(A)(1) Construction sites and construction activities. construction sites and operations shall be required to maintain during and after all construction, development excavation or alteration operations, structural and non-structural best management practices with the intent to reduce pollutants and sediment in stormwater runoff.

FBC A201.1 This code establishes standards for accessibility to places of public accommodation and commercial facilities by individuals with disabilities. All new or altered public buildings and facilities, private buildings and facilities, places of public accommodation and commercial facilities subject to this code shall comply with 2017 FBC Accessibility.

FBC A221.1.1 Florida vertical accessibility. Nothing in this code relieves the owner of any building, structure, or facility governed by this code from the duty to provide vertical accessibility to all levels above and below the occupiable grade level, regardless of whether the ADA standards for accessible design require an elevator to be installed in such building, structure or facility.

FBC A206.2.1 Site arrival points. At least one accessible route shall be provided within the site from accessible parking spaces complying with FBC A502 and accessible passenger loading zones complying with FBC A209; public streets and sidewalks; and public transportation stops to the accessible building or facility entrance they serve.

FBC_BCA 107.3.4.0.6 Compliance with the specific minimum requirements of this code shall not be in itself deemed sufficient to assure that a building or structure complies with all of the requirements of this code. it is the responsibility of the architect and/or engineer of record for the building, structure or facility to determine through rational analysis what design requirements are necessary to comply with 2017 FBC.

1. FBC_BCA 107.1 As per the building official, separate building applications will be required for erosion control, site work.

2. FBC 1003.1 The enforcing agency will require that all general requirements specified in sections 1003 through 1013, applicable to all three elements of the means of egress system, in addition to those specific requirements for the exit access, the exit and the exit discharge, comply with this section of the code.

3. FBC_BCA 107.1.1 The enforcing agency will require a life safety plan illustrating the floor area with proposed alterations with each room labeled. indicate construction type, fire rated walls, occupancy type: (current and proposed), occupancy load, means of egress, common path/travel distance/dead end corridor limits, accessibility accommodations including areas of refuge if applicable, emergency lighting, exits/exit signage, fire extinguishers, smoke alarms, fire suppression system and pull stations if applicable. Also provide tested design from accepted agency for rated walls and penetration details.

4. FBC_BCA 107.3.5.2 The enforcing agency will require that all shop drawings, (i.e. components attached to building structure, , fence and gates…etc), necessary to show compliance with applicable codes; shall be approved by the architect or professional engineer and submitted to the building official prior to installation.

5. F.S. 481.221(2) The enforcing agency will require digital signature panel to be active on all documents submitted for review to authenticate the serial number matches the submitted ESA. F.A.C. 61g1-16.005 Each sheet is required to be digitally or electronically signed, and bear the impress seal of, an architect or engineer (FBC_BCA 107.3.4.0.1).

6. FBC_BCA 107.3.4.0.8 All plans and/or specifications prepared by an architect or an engineer pursuant to the requirements of this code shall be hand signed, dated and sealed.

7. FBC A208.2 Minimum number. Parking spaces complying with 502 shall be provided in accordance with table 208.2 except as required by 208.2.1, 208.2.2, and 208.2.3. Where more than one parking facility is provided on a site, the number of accessible spaces provided on the site shall be calculated according to the number of spaces required for each parking facility.

8. FBC A208.2.3.3 Parking for guests, employees, and other non-residents. Where parking spaces are provided for persons other than residents, parking shall be provided in accordance with table 208.2.

9. FBC A502.6 The enforcing agency will require parking space identification comply with the following code: signs shall include the international symbol of accessibility complying with FBC A703.7.2.1. Signs identifying van parking spaces when required By FBC A502.2 shall contain the designation “Van Accessible.” Reference Engineering Standard 300-5.

10. FBC 3303.5 Water Accumulation. The enforcing agency will require provisions be made to prevent the accumulation of water or damage to any foundations on the premises or the adjoining property.

11. 1804.4 Site Grading. The ground immediately adjacent to the foundation shall be sloped away from the building at a slope of not less than one unit vertical in 20 units horizontal (5-percent slope) for a minimum distance of 10 feet measured perpendicular to the face of the wall. If physical obstructions or lot lines prohibit 10 feet of horizontal distance, a 5-percent slope shall be provided to an approved alternative method of diverting water away from the foundation. Swales used for this purpose shall be sloped a minimum of 2 percent where located within 10 feet of the building foundation. Impervious surfaces within 10 feet of the building foundation shall be sloped a minimum of 2 percent away from the building.

12. FBC_BCA 110.13.2.1 It shall be the joint responsibility of any owner of real property upon which construction is occurring, and any contractor responsible for said construction, to ensure that all road rights-of-way remain free at all times of all construction waste and trash resulting from such construction, and that all waste and trash resulting from the construction are contained on the real property upon which the construction occurs.

13. FBC_BCA 109.3 Building Permit Valuations. The applicant for a permit shall provide an estimated permit value at a time of application. Permit valuations, shall include total value of work, including materials and labor, for which the permit is being issued, such as electrical, gas, mechanical, plumbing equipment and permanent systems.

14. FBC_BCA 110.8.5.4 All plans for the building which are required to be signed and sealed by the architect or engineer of record contain a statement that, to the best of the architect’s or engineer’s knowledge, the plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards as determined by the local authority in accordance with this section and chapter 633, Florida Statutes.

 

 

BSO

Plan Reviewer: Scott Longo | scott_longo@sheriff.org

Status: Review Complete Pending Development Order

 

Disclaimer:
The services of an independent, experienced, qualified and certified Security Crime Prevention/ CPTED Consultant are highly recommended for objective and credible security review integrity.
This review does not guarantee a crime will never occur; it is an effort to mitigate opportunities for crime and to help avoid any present and future security deficiencies, conflicts, or liabilities that might occur without any review.

Miscellaneous: CPTED & Security Strengthening
a. Ensure all exterior electrical power outlets have a lock or power secure internal cutoff switch to deny unauthorized use by vagrants, etc. who loiter and trespass to charge their mobile phones, etc.
b. Ensure all exterior water outlet spigots have a secure locking cap to deny unauthorized use by vagrants, etc. who loiter and trespass to wash themselves and their clothes, and who leave soiled clothing and lots of litter behind.

 

 

CRA

Kimberly Vazquez | kimberly.vazquez@copbfl.com

Status: Review Complete, No Comments.

 

No comments.

 

 

UTILITIES

Plan Reviewer: Nathaniel Watson | nathaniel.watson@copbfl.com

Status

 

Comments not provided by 4/25/22. Contact Nathaniel Watson directly for comments.

 

 

LANDSCAPE REVIEW

Plan Reviewer: Wade Collum | wade.collum@copbfl.com

Status: Review Complete Resubmittal Required

 

1. Show on the plans and provide a dumpster detail including hedges in accordance with 155.5301.C
2. Submit a tree survey prepared, signed, and sealed by a Florida Registered Surveyor showing the locations of all existing trees and palms in accordance with Code Section 155.2411, and Part 5 for specifically the large tree location in the NW corner.
3. Submit a Tree Appraisal prepared by an ISA Certified Arborist in accordance with Rule 14-40.030 of the Florida Administrative Code as amended, for all trees and palms that are specimen size , and DBH for caliper for all nonspecimen trees, that assigns each existing tree a number; that specifies the common and botanical name for each existing tree; describes the overall size and caliper of each existing tree; evaluates the health condition of each existing tree; identifies the status of each existing tree (whether the tree is to be protected in place, be relocated, or be removed); and provides a dollar value for each existing tree included on the tree survey.in accordance with Code Section 155.2411, and Part 5.
4. Verify and provide pervious area calculations and show them on a plan to be only within the property lines.
5. Remove ranges in sizes of trees.
6. Provide an elevations sheet as building height is used to establish minimum tree heights and VUA landscaping
7. As per 155.5203.B.2.ii.Based on the height of the building half of all required canopy trees are to be 14 / 16’ tall and palms to be 18’ / 22’ OA, please adjust.
8. Show how requirements from 155.5203.D.5 VUA Landscaping are being met. Provide up to 24’ of landscape areas between a vehicular use area and an abutting building.
9. Show on the plans and provide a dumpster detail including hedges in accordance with 155.5301.C.
10. Provide a photometric plan clearly showing pole locations. Show poles and radii on the landscape plan.
11. As per 155.5401.C. remove light poles from required VUA areas, perimeter landscaping strips, landscaped islands in parking bays, landscaped areas between parking bays, and landscaping between vehicular use areas and buildings.
12. Provide 10’ wide VUA requirements as per 155.5203.D with trees and shrubs along all perimeters of the site. Relocate vehicle lift so that buffer extends East to the building. Add 1 additional canopy tree along the north property line
13. As per 155.5203.D.4., a landscaped island shall be provided at each end of every row of parking spaces and per every 10 spaces. Landscape parking islands are to be a minimum 8’ wide and contain trees, sod and irrigation for all new parking areas. Palms do not qualify.
14. Show sod on the plan.
15. Provide a mechanical equipment screening detail.
16. All tree work will require permitting by a registered Broward County Tree Trimmer.
17. Provide a comment response sheet as to specifically how comments have been addressed at time of resubmittal.
18. Additional comments may be rendered a time of resubmittal.

 

 

ZONING

Plan Reviewer: Lauren Gratzer | lauren.gratzer@copbfl.com  

Status: Resubmittal Required

 

1.                     The scope of work for the proposed site plan has drastically changed since the original DRC submittal in January 2021. A 6,672 SF addition to the building will result in this application changing from a minor site plan to a major site plan with building design. A new fee for this application change is now required. As of this submittal, it appears the use will be “Used Automobile and Light Truck Sales with Indoor Display Only” and will be reviewed as such until informed otherwise.

2.                     Note: The I-1 Zoning District, in which this property is located in, requires an interior side yard setback of 10’ on either side of the building and a rear yard setback of 30’ (155.3402). Buildings 1 and 2 are legally non-conforming to these setbacks. The remainder of this property shall be brought up to current Code requirements.

3.                     Provide an updated project narrative outlining all proposed work of this site plan. Additionally, list all business uses that have existing Business Tax Receipts (BTRs) or plan to have future BTRs at this location. BTR records indicate there is a contactor’s office in building 2 and the Specialty Auto Leasing LLC with approval as “Used Automobile and Light Truck Sales with Indoor Display Only” in building 1. Clarify if any other businesses plan to come into the existing or proposed building. This will be used to determine the parking requirements.

4.                     Clarify in the narrative and on the site plan if any cars are proposed to be kept outdoors for display. If no cars are proposed to be kept outdoors, place a note on the site plan stating, “There shall be no outdoor storage, display, or activity” (in addition to adding to the project narrative).

5.                     Clarify in the narrative if services such as automobile service, repair, installation, and/or maintenance will be provided at this location. This may trigger landscaping requirements.

6.                     Clarify in the narrative how the western most building is being modified, as stated on the site plan.

7.                     Clarify in the narrative how the automobiles will be loaded into the buildings. The site plan does not show a clear path for the cars to enter the building.

8.                     Provide both addresses as the “project address” on the site plan: 929 SW 8th ST & 941 SW 8 ST, as this site plan is for both properties.

9.                     Revise the scope of work (plan proposal) stated on the site plan to include the addition of the 6,672 SF building and upgrading the landscaping.

10.                     Comment not addressed: Update the parking table on the site plan to include the formulas & calculations for the minimum number of parking spaces required per 155.5102.D.1. Include a ‘Provided vs Required’ parking data table on the site plan.  A contractor’s office requires 1 parking space per 400 sf. A “Used Automobile and Light Truck Sales with Indoor Display Only” requires 1 space per 400 SF of indoor sales display area and office space. Additionally, include any other type of business that may be proposed here.

a.                     With the numbers provided on the site plan, the contractor’s office in the western building requires a minimum of 9 parking spaces. The new 6,672 SF building will require 17 parking spaces. The existing building, closest to I-95, may continue to operate with the 1978 Variance approval of three parking spaces. Therefore, the minimum required parking on site is 29. The proposed site plan is deficient in parking by 15 parking spaces. Revise the plans.

11.                     Comment not addressed: Note on the site plan that all parking will be double striped (155.5102.C.4).

12.                     All parking areas must have a continuous curb (155.5102.C.9). Provide this on all plans.

13.                     Provide the width of the regular parking spaces on the site plan. Parking spaces shall be at least 9’x18’ (155.5102.I.1).

14.                     Comment not addressed: The vehicular use area perimeter buffer shall be a minimum 10’ in width per 155.5203.D.3. The 2’-9’’ buffer on the east side is not sufficient and will require relief.

15.                     The curbing shown on the site plan appear to disappear in the southeast corner as it reaches the vehicle lift. However, it is shown properly on the landscape plan. Correct this error on the site plan and provide the proper curbing in this landscape area.

16.                     Revise the landscape plan in all areas that say “new lawn” to state it as “sod”.

17.                     Provide a detail of the dumpster enclosure. Call out the height, materials, and color. It shall be constructed of brick, masonry, stone, or similar material, and on the fourth side by a wood or metal gate. The color shall match the design of the building. The height of the screening walls and gate shall be at least six inches higher than the height of the container (155.5301.C.1.a).

18.                     Provide landscaping surrounding the dumpster enclosure per 155.5301.C.1.a. in order to soften its visual impact.

19.                     The I-1 Zoning District requires a minimum of 20% pervious area inside of the property lines. The square footage required to meet this code requirement does not include the landscaping outside of the property, in the City swale. It appears the total landscape area number provided on the site stats chart of the site plan includes the swale landscaping. Additionally, permeable pavement shall not be credited towards the minimum pervious area of a property. Revise this to only include the landscaping inside of the property lines and ensure it still meets the minimum 20% of the lot.

20.                     Architectural elevations were not provided with this upload. Provide signed and sealed elevations for all sides of all buildings. Provide the height of the buildings as follows: “The height of a structure shall be determined by measuring the vertical distance from the average elevation of the existing finished grade at the front of the structure to the top of the roof for a flat roof, to the deck line for a mansard roof, or to the mean height between eaves and ridge for a gable, hip, cone, gambrel, or shed roof” (155.9401.G).

21.                     Provide the existing and proposed setbacks of the buildings on the site plan as both dimensions and within a site data table.

22.                     Clarify the note that says “SET BACK” in the southwest corner of the site plan, under the wording for “stop sign”. This set back wording doesn’t appear to represent anything. Likewise, clarify what setback you are calling out in the northwest corner of building 2. Is this a 10’ setback to the proposed concrete walkway?

23.                     Clarify why there is a 10’ landscape dimension called out from the northern property line. Provide the full extent of the landscape area dimension in the area.

24.                     Clarify what the 16’-6’’ dimension represents in the southeast corner of the site plan. It appears to run from the property line to a random point in the drive aisle.

25.                     Provide the width of the sidewalk where the bike racks are located.

26.                     Provide the total number of bicycle spaces in the site data table on the site plan.

27.                     There is currently no mechanical equipment rendered on the site plan and there was no roof plan or elevation sheets provided. Any ground floor mechanical equipment must be at least 3 feet from the property line and screened with either a solid fence or dense landscaping per 155.5301.A.  Mechanical equipment mounted on the roof of a building shall be screened by a parapet wall, roof screen, or similar device of a height equal to or exceeding the height of the mechanical equipment being screened. Note that mechanical equipment is not permitted to be placed in front of the principal structure. If the mechanical equipment will be placed on the roof, show this on the elevations. If it will be on the ground, show it on the site plan.

28.                     Provide details of the lighting fixtures. Any light source or lamp that emits more than 900 lumens shall be concealed or shielded with full cut-off style fixture with an angle not exceeding 90 degrees to minimize glare and unnecessary light diffusion onto adjacent properties and streets (155.5401.G).

29.                     Wall packs on buildings may be used at entrances to a building to light unsafe areas. They are not intended to draw attention to the building or provide general building or site lighting. Wall packs on the exterior of the building shall be fully shielded (e.g., with true cut-off type bulb or light source not visible from off-site) to direct the light vertically downward and have a light output of 900 lumens or less (155.5401.I).

30.                     Provide a table on the photometric plan that states how many poles and how many wall light fixtures are being proposed in addition to the specific manufacturing information for each.

31.                     Clarify why a wall mounted light is proposed on the southern property line fence. A wall mounted light should not be on a fence.

32.                     Clarify where the proposed light poles are located. They are not shown on the photometric plan but they are in the legend.

33.                     Provide the height of each light pole and wall mounted fixture on the photometric plan. The maximum light height is 30 feet (155.5401.D).

34.                     Elevations were not provided and therefore a review of the building design could not be assessed. Provide elevations and ensure it meets the requirements of Code section 155.5602: Commercial, Institutional, and Mixed-Use Design Standards.

a.                     Provide the width and height on the elevations. “Street-facing front building facades that are greater than 60 feet wide shall be articulated with wall offsets (e.g., projections or recesses in the facade plane) that are at least one foot deep, at least ten feet wide, and spaced no more than 40 feet apart” (155.5602.C.5.a). Subsection B in the Code, has offset alternatives.

b.                     Call out the materials on the elevations and adhere to Code section 155.5602.C.6.Facade Materials.

c.                     Provide the fenestration calculations and adhere to Code section 155.5605.C.7.Fenestration/Transparency.

35.                     Provide a sustainability narrative that outlines how this project aims to achieve at least 12 sustainability points as defined in Table 155.5802: Sustainable Development Options and Points.

36.                     Landscaping shall meet the requirements of Code section 155.5203.Landscaping, including but not limited to the base building plantings and the parking space islands for every 10 spaces.

37.                     Additional comments may be rendered upon future submittals.

 

 

 

SOLID WASTE AND RECYCLING

Plan Reviewer: Beth Dubow | beth.dubow@copbfl.com

Status: Review Complete Pending Development Order

 

NOTE: Owners of this commercial property are responsible for securing garbage collection service directly from Waste Management, Inc. or the current City franchise collector.


NOTE: Recycling collection is not required, but it is encouraged. Recycling collection service may be obtained from a recovered materials hauler.


NOTE: As stated in the Pompano Beach Code of Ordinances, Chapter 96, including Section 96.12(D)(1), all construction and demolition debris removal is the responsibility of the owner. All solid waste generated within the geographic boundaries of Pompano Beach shall be collected by the franchise collector (Waste Management at the time of this writing) and disposed of as directed by the city disposal agreement. All materials shall be generated from the property on which the materials are placed for removal. Information regarding container size and hauling costs may be found in Chapter 96, Section 96.13.


NOTE: Additional comments may be necessary based upon revisions, additional plans and/or documents. Contact Beth Dubow at 954-545-7047 or beth.dubow@copbfl.com should you have any questions or concerns regarding this review.

 

 

PLEASE NOTE: Applications that require resubmission to the DRC have 45 days from the time of original DRC meeting in which to resubmit. Applications that fail to be resubmitted before the completion of these 45 days, or fail to receive a time extension from the Development Services Director, shall be considered withdrawn (§155.2304.B).